Connecting the current sensors for hybrid inverter

 

Connecting the current sensors for hybrid inverter

Question: I wish to connect a hybrid inverter. This means that the inverter is both working as a charger (from grid/solar to battery) and as a load (discharge the battery).  How do I connect the current sensors?

Answer: In this configuration you need only connect the “Consumer” (Load Currents sensor -  OUT). This sensor supports the counting of the current in both directions of the flow. The other sensor (Charger current sensor – IN) will not be connected.